• I/O Type: 7 RTD
  • 10/100Based-T Ethernet
  • Supports multi-channel/multi-range
  • Pt 100/1000, Ni, Balco 500
  • Wiring burn-out detect function

  • 產品介紹
    The ADAM-6015 7-channel RTD input module accepts a wide range of RTD sensor types, including Pt100, Pt1000, Ni50, Ni508, and Balco 500 series. Multi input ranges are allowed in one module, creating a cost-effective solution. Most important of all, the ADAM-6015 supports open wiring diagnostic function which warns operators when the sensor wire has been broken. It specifically aims at building and factory temperature monitoring applications.

    Display LED Indicators Status, Comm, Link, Speed
    Power Supply Power Requirement 10~30 VDC
    Analog Input Channels 7 (2 or 3-wired)
    Direct Sensor Input RTD (Pt, Balco, or Ni)
    Burn-out Detection Yes
    Channel Independent Configuration Yes
    Sampling Rates 10 samples/second
    Resolution 16-bit
    Input Impedance >10 MOhm
    Span Drift ±25 ppm/°C
    Zero Drift ±6 µV/°C
    CMR @ 50/60 Hz 90 dB
    NMR @ 50/60 Hz 60 dB
    General Watchdog Timer System (1.6 second) & Communication (programmable)
    Connectors 1 x RJ-45 (LAN) & 2 x plug-in terminal block (I/O and power)
    Temperature (Operating) -10~70 °C (14~158 °F)
    Humidity 20~95 %RH
    Temperature (Storage) -20~80 °C (-4~176 °F)
    Interface 10/100Base-T(X)
    Peer-to-Peer Yes
    GCL Yes
    Isolation Protection 2000 VDC
    Communication Protocol Modbus/TCP, TCP/IP, UDP, and HTTP
    Communication Speed Ethernet: 10/100Mbps
    Comm. Distance Ethernet: 100 m