ADAM-4016

ADAM-4016

  • Strain Gauge Input
  • Watchdog Timer

  • 產品介紹
    A strain gauge input module uses a microprocessor-controlled integrating A/D converter to convert sensor voltage or current signals into digital data for load cell and stress measurement. The digital data is then translated into either engineering units, twos complement hexadecimal format or percent-age of full-scale range (FSR)according to the module ’s configuration. When prompted by the host computer, the data is sent through a standard RS-485 interface. The strain gauge input module offers signal conditioning, A/D conversion, ranging, and RS-485 digital communication functions. They protect your equipment from ground loops and power surges by providing opto-isolation of the A/D input and transformer based isolation up to 3000 VDC .

    產品規格
    ADAM-4016-A2E
    Display LED Indicators Power
    Power Supply Power Requirement 10~30 VDC
    Analog Input Channels 1 differential
    Voltage Range ±15 mV ±50 mV ±100 mV ±500 mV
    Current Input ±20 mA
    Sampling Rates 10 samples/second
    Resolution 16-bit
    Input Impedance Voltage: 2 MOhm Current: 125 Ohm
    Span Drift ±25 ppm/°C
    Zero Drift ±6 µV/°C
    CMR @ 50/60 Hz 92 dB
    Analog Output Channels 1
    Voltage Range 0~10 V (30 mA max.)
    General Watchdog Timer System (1.6 second)
    Connectors 2 x plug-in terminal block (#14~22 AWG)
    Temperature (Operating) -10~70 °C (14~158 °F)
    Humidity 5~95 %RH
    Temperature (Storage) -25~85 °C (-13~185 °F)
    Interface RS-485
    Isolation Protection 3000 VDC
    Communication Protocol ASCII command
    Communication Speed Serial: From 1,200 to 115.2 k
    Comm. Distance Serial: 1.2 km
    Data Flow Control Yes
    Digital Output Channels 4 Open collector to 30V, 30 mA max. load
    Power Dissipation 300 mW

    * 上述商品規格僅供參考,實際規格以實物為準。