General
|
Power Consumption
|
1.4 W @ 24 VDC
|
Supported Protocols
|
ASCII command
|
Analog Input
|
Channels
|
1
|
Input Impedance
|
Voltage : 2 MΩ
Current : 125 Ω
|
Input Type
|
T/C, mV, V or mA
|
Input Range
|
±15 mV , ±50 mV , ±100 mV , ±500 mV , ±1 V ,
±2.5 V , ±20 mV
|
Accuracy
|
Voltage mode : ±0.1% or better
Current mode : ±0.2% or better
|
T/C Type and Temperature Range
|
J
|
0~760°C
|
R
|
500~1,750°C
|
K
|
0~1,370°C
|
S
|
500~1,750°C
|
T
|
-100~400°C
|
B
|
500~1,800°C
|
E
|
0~1,000°C
|
|
|
Span Drift
|
±25 ppm/°C
|
Zero Drift
|
±6 µV/°C
|
Digital Input
|
Channels
|
1
Logic level 0 : 1 V max.
Logic level 1 : 3.5~30 V
Pull up current : 0.5 mV
10 kΩ resistor to 5 V
|
Event Counter
|
Max. input freq : 50 Hz
|
Digital Output
|
Channels
|
2 , open collector to 30 V, 30 mA max. load
|
Power Dissipation
|
300 mW
|
Supports high / low alarms
|